Megger TDR2000/2RM (134 pages)
Languages available:
No exact matches found. Please change your query
Need help?
Do you have a question about the product that is not answered in the manual?
- Receive updates on solutions
- Get answers to your question
Product description:
Frequently Asked Questions
What safety precautions should be taken when using the TDR2000/2?
The TDR2000/2 meets IEC 61010 safety standards up to 300V CAT III. Although it does not generate hazardous voltages, it can be connected to circuits that may pose electric shock or arcing risks. Users must ensure their own safety by verifying SELV levels before touching accessible parts and using appropriate insulated gloves. Always disconnect test leads before accessing the battery compartment.
What is the maximum voltage rating for the TDR2000/2?
The TDR2000/2 is rated for use on energized systems up to 300V Installation Category III. It should not be used on primary supply circuits such as overhead cables. A fused clip set must be used for connecting to live systems.
What is the purpose of the 4mm plug to BNC adaptor?
The 4mm plug to BNC adaptor is intended for use with telecom network cables only. It is not designed for direct connection to an energized mains supply. However, it may be subject to telecom network voltages as defined by IEC 60950. The outer sheath is normally at SELV levels but may carry hazardous voltages under single fault conditions.
How do I replace the battery in the TDR2000/2?
When the battery low symbol appears, replace the alkaline IEC LR6 (AA) cells or 1.2V rechargeable cells. Switch off the instrument, disconnect test leads, remove the battery cover, and replace the cells ensuring correct polarity. Refitting the battery holder is the reverse of removal.
What is the function of the Tx Null feature?
The Tx Null feature allows the user to reduce the amplitude of the transmitted pulse on the displayed trace, making it easier to identify reflections close to the start of the cable, typically referred to as the 'Dead Zone'. This helps in detecting faults near the cable's beginning.
How do I measure the distance to a fault using the TDR2000/2?
Use the 'Find' key to locate the furthest major change in impedance, which may indicate a fault or the end of the cable. Adjust the gain, zoom, and cursor position for accurate measurement. The distance is then read directly from the display using the velocity factor (VF) set in the TDR.
What is the velocity factor and how is it used?
The velocity factor (VF) is a setting that determines how fast the signal travels through the cable relative to the speed of light. It is used to calculate the distance to a fault. The VF can be set between 0.300 and 0.999 and is crucial for accurate distance measurements.
How do I adjust the gain on the TDR2000/2?
The gain setting allows adjustment of the instrument's sensitivity from 0 dB to 90 dB in 6 dB increments. Increasing the gain makes small impedance changes more visible, helping to identify faults. However, excessive gain may amplify noise, so it should be adjusted carefully.
What is the purpose of the 'Save' function?
The 'Save' function toggles the display between an active trace and one of 15 stored memory locations. This allows users to store and recall traces for comparison or later analysis. Saving a trace enables the user to revisit and compare results with real-time measurements.
How do I set the zero point for distance measurements?
The zero point can be set using the 'ZERO (ns)' setting, which adjusts the instrument's reference point to the end of the test leads. This ensures that the test lead length is automatically deducted from any distance calculation, providing accurate fault location measurements.