Product description:
Frequently Asked Questions
What are the display capabilities of the device?
The device features programmable displays with a wide selection of inputs and outputs for displaying temperature, volume, and weight. It supports linearisation, scaling, and difference measurement functions for programming via PReset software.
What interfaces are available for signal communication?
The device includes interfaces for analogue and digital signals as well as HART® signals, enabling communication between sensors, I/P converters, frequency signals, and control systems in Ex zones 0, 1, 2, and some modules in zones 20, 21, and 22.
What isolation features does the device offer?
The device provides galvanic isolators for analogue and digital signals as well as HART® signals. It offers a wide range of both loop-powered and universal isolators with features like linearisation, inversion, and scaling of output signals.
What temperature transmitter options are available?
The device offers a wide selection of transmitters for DIN form B mounting and DIN rail modules, supporting both analogue and digital bus communication. Options range from application-specific to universal transmitters.
What are the key features of the universal modules?
Universal modules are programmable via PC or front panel, offering flexible input, output, and supply options. They include advanced features such as process calibration, linearisation, and auto-diagnosis.
What functions does the signal calculator support?
The signal calculator supports a variety of functions including addition, subtraction, maximum/minimum selection, multiplication, division, power calculation, and root extraction. It also includes sample-hold, peak-hold, delay, and signal limiting functions.
How does the sample-hold function work?
The sample-hold function captures the current input value and holds it constant as long as the digital input is active. When the digital input is inactive, the output follows the input value.
What is the purpose of the peak-hold function?
The peak-hold function stores the highest input value recorded since the last reset. When the digital input is activated, it resets the output to the current input value.
What is the function of the delay feature?
The delay function transfers the input value to the output after an exponential curve (R/C time constant), where the time constant can be set by the user.
What are the key parameters of the PID regulator?
The PID regulator includes proportional band (XP), integral time (TI), and derivative time (TD) parameters. These can be set internally or externally as current or voltage signals, with options for direct or inverted regulation.