Refu sol 020K-SCI (199 pages)
Tags
Languages available:
No exact matches found. Please change your query
Need help?
Do you have a question about the product that is not answered in the manual?
- Receive updates on solutions
- Get answers to your question
Product description:
Frequently Asked Questions
What is the maximum operating temperature for the REFUsol® inverter?
The inverter housing can reach a surface temperature of 75°C when the ambient temperature is 45°C. It is important to allow the device to cool for 15 minutes before touching to avoid burns.
What safety precautions should be taken when handling the REFUsol® inverter?
Never touch the inverter or its components while it is powered on. Even after turning off, dangerous voltages may still be present inside. Always ensure the device is properly grounded and follow all safety instructions to prevent electric shock or injury.
How should the REFUsol® inverter be mounted?
The inverter is designed for vertical mounting on a wall using a self-centering mounting plate. Ensure the mounting location is well-ventilated, free from flammable materials, and at eye level for optimal accessibility. Maintain minimum distances of 50 mm from the sides, 500 mm from the top and bottom, and from adjacent equipment.
What is the recommended grounding procedure for the REFUsol® inverter?
The inverter must be grounded using the provided grounding bolt. A separate grounding connection should be made to the housing, and the grounding wire should have a cross-sectional area larger than the main power cable (minimum 10 mm²). The grounding wire should be installed at maximum distance and not parallel to the main power cable to avoid interference.
What are the requirements for connecting the PV generator to the inverter?
PV strings must be connected under no-load conditions, preferably in darkness, to avoid dangerous voltages. Ensure correct polarity for all connections, and use MC4 connectors with appropriate cable cross-sections. Always verify the open-circuit voltage is below 50 V before connecting.
What are the recommended cable cross-sections for DC connections?
For DC connections, use cables with cross-sections between 3-6 mm² for PV-KST4/6I-UR and PV-KBT4/6I-UR connectors, and 5.5-9 mm² for PV-KST4/6II-UR and PV-KBT4/6II-UR connectors. Ensure all unused connections are sealed with blind plugs to maintain the IP65 protection rating.
What are the safety requirements for AC connection?
The AC connection must use a 5-core cable with the protective earth (PE) conductor connected at all times. Ensure the power supply is disconnected before connecting the inverter, and verify the voltage is not higher than 265 V (phase to neutral). Always use proper insulation and follow local electrical codes for installation.
What should be done if the inverter detects a fault in the PV generator?
If the inverter detects a fault in the PV generator's insulation, it will automatically shut down. Before reconnecting, the insulation fault must be resolved to ensure safe operation. Always check the insulation resistance and repair any issues before reconnection.
What is the purpose of the country code setting on the inverter?
The country code setting ensures compliance with local electrical regulations and grid requirements. It must be set correctly to avoid operational issues or disconnection from the grid. The country code can only be changed by authorized service personnel after it has been set and confirmed.
What are the recommended maintenance procedures for the inverter?
Regularly inspect the inverter for signs of damage, overheating, or loose connections. Ensure all external connections are secure and properly insulated. Clean the inverter periodically to prevent dust buildup, and check the grounding and insulation resistance as part of routine maintenance.