Product description:
Frequently Asked Questions
What is the purpose of the 8DI NAMUR electronic module?
The 8DI NAMUR electronic module is used to evaluate NAMUR sensors and process both switched and unswitched mechanical contacts. It is designed for use in hazardous areas and supports intrinsically safe applications.
Where is the 8DI NAMUR module installed?
The 8DI NAMUR module is installed into the TM-IM/EM or TM-EM/EM terminal module. It must be securely connected to ensure proper operation and compliance with safety standards.
What safety certifications does the 8DI NAMUR module have?
The 8DI NAMUR module is certified for ATEX, IECEx, and CE standards. It is rated for use in explosive environments with device categories 2G, 1G, 3G, 1D, 2D, and 3D, depending on the zone.
How should the 8DI NAMUR module be mounted in hazardous zones?
In Zone 1, the module must be mounted in an enclosure with Ex e protection. In Zone 2, it must be mounted in an enclosure with at least IP 54 protection. Always ensure the manufacturer's documentation is followed.
What are the wiring requirements for the 8DI NAMUR module?
Wiring must follow EN 60 079-14 and local regulations. Intrinsically safe and non-intrinsically safe lines must be separated and run in separate cable ducts. The module's terminals are detailed in the ET 200iSP manual.
What are the maximum current and power consumption values for the 8DI NAMUR module?
The module consumes up to 70 mA when connected to 8 NAMUR sensors and up to 90 mA with unswitched contacts. The maximum power loss is 0.84 W for NAMUR sensors and 1.1 W for unswitched contacts.
What safety data is required for the sensors connected to the 8DI NAMUR module?
The safety data (maximum values) of the sensors must match the corresponding values of the 8DI NAMUR module. These values are specified in the Ex certificate and must comply with EN 60 079-14.
How should the 8DI NAMUR module be handled during installation?
Installation must be performed in non-explosive conditions. Ensure the module is undamaged before installation, and follow all EN 60 079-14 guidelines. The mechanical coding on the module must not be altered.
Where can I find the latest wiring and configuration details for the 8DI NAMUR module?
The latest wiring and configuration details are provided in the ET 200iSP manual. The control drawing for the system is also available online at the Siemens website under the specified reference.
What should be done if the 8DI NAMUR module requires repair?
If repair is needed, the module must be returned to Siemens AG, Elektronikwerk, at the specified address. Repairs must only be performed by the manufacturer to ensure compliance with safety and technical standards.