Elecro EVOLUTION (76 pages)
Tags
Languages available:
No exact matches found. Please change your query
Need help?
Do you have a question about the product that is not answered in the manual?
- Receive updates on solutions
- Get answers to your question
Product description:
Frequently Asked Questions
How should the heater be positioned?
The heater should be horizontally or vertically mounted, allowing enough space for pipe connections and wiring. It must be securely fixed to a firm base or wall. Refer to the foot position diagram for installation details.
What is the minimum pipe size required?
The pipe work connecting to and from the heater must have a minimum bore (internal diameter) of 1¼” (32mm). The return pipe should include a safety loop or 'kick-up' near the heater to ensure it remains full of water during operation.
How to reverse the flow direction?
To reverse the flow, rotate the flow switch 180 degrees. Ensure the arrow on the flow switch is aligned with the water flow. Avoid lifting the paddle more than 5mm from its housing to prevent damage.
What are the minimum flow rates for the heater?
The minimum flow rate for 2–6 kW heaters is 1,000 litres/hour (220 UK gallons/hour), and for 9–24 kW heaters, it is 4,000 litres/hour (880 UK gallons/hour). Exceeding these rates may require a bypass to protect the heater elements.
What water quality parameters are required?
Water quality must meet the following limits: pH 6.8–8.0, Total Alkalinity 80–140 ppm, Chloride Content MAX 150 mg/litre, Free Chlorine 2.0 mg/litre, Total Bromine MAX 4.5 mg/litre, and TDS/Calcium hardness 200–1,000 ppm.
How long does it take to heat the pool?
Assuming no heat losses and a heater sized at 1.5 kW per 1,000 UK gallons of water, it will take approximately 2 days of continuous operation to raise the pool temperature from tap to swimming temperature. Heat loss, especially in cold weather, will slow the process.
How to test the heater's function?
For a quick test, observe the electricity meter when the heater is on (red light) and when it is in standby (amber light). The meter should show higher energy usage when the heater is active. For an accurate test, take two meter readings with a one-hour interval and calculate the energy consumed.
What should I do if the heater won't switch to 'On'?
The heater may not switch from standby to on if the set point temperature is reached or if the thermal safety cut-out has tripped. Check the temperature setting and reset the cut-out by pressing the red button. Investigate debris or air pockets in the flow tube if the issue persists.
What electrical requirements are needed?
The heater must be connected according to local regulations and installed by a qualified electrician. The power supply must include an RCD. The cable size should be calculated at 5 amps per mm² for distances up to 20 meters, with adjustments for longer runs.
How to ensure proper operation after installation?
After installation, run the water-circulating pump to purge air from the system and heater. Ensure the flow switch is correctly aligned with the water flow, and verify that the minimum flow rates are met for the heater to operate properly.