Product description:
Frequently Asked Questions
What is the operating range of the AS-i Safety Monitor?
The AS-i Safety Monitor is designed for use in electrical operating rooms or switchgear with a minimum protection class of IP54. It is suitable for safety applications up to category 4 according to ISO 13849-1, with PLe certification.
What are the electrical specifications of the AS-i Safety Monitor?
The operating voltage is 24V DC with a tolerance of ±15%. The rated operating current is 150mA for ASM1/1 and ASM1E/1, 200mA for ASM1/2, ASM1E/2, and ASM2/1, and 250mA for ASM2E/2. All types have a maximum current draw of 600mA. The response time is less than 40ms.
What are the physical dimensions of the AS-i Safety Monitor?
The dimensions of the AS-i Safety Monitor are 45mm x 105mm x 120mm. The housing material is polyamide PA 66. The weight varies depending on the model: approximately 350g for ASM1/1 and ASM1E/1, 420g for ASM2E/1, and 450g for ASM1/2, ASM1E/2, and ASM2E/2.
What are the mounting requirements for the AS-i Safety Monitor?
The AS-i Safety Monitor is mounted using a snap-fit mechanism on a DIN rail according to EN 50022. The mounting requires a 37x118 or 37x139 mm footprint, depending on the model.
What are the connection specifications for the AS-i Safety Monitor?
The AS-i Safety Monitor uses a 5 to 6 mm / PZ2 connector. The tightening torque is between 0.8 and 1.2 Nm (7 to 10.3 LB.IN). The cable cross-sections are 1 x (0.5 to 4.0) mm² and 2 x (0.5 to 2.5) mm² for standard connections, and 1 x (0.5 to 2.5) mm² and 2 x (0.5 to 1.5) mm² for other connections.
What are the safety outputs of the AS-i Safety Monitor?
The AS-i Safety Monitor has a safety output with potential-free closing contacts. The maximum contact load is 1A DC-13 at 24V DC and 3A AC-15 at 230V AC. The safety output is a PNP transistor output with a current capacity of 200mA, featuring short-circuit and polarity protection.
What are the environmental conditions for the AS-i Safety Monitor?
The operating temperature range is from -20°C to +60°C, and the storage temperature range is from -30°C to +70°C. The protection class is IP20, ensuring protection against solid objects larger than 12.5mm.
What are the communication specifications for the AS-i Safety Monitor?
The AS-i Safety Monitor uses an RS 232 interface with a baud rate of 9600, no parity, 1 start bit, 1 stop bit, and 8 data bits. It has an input for 'Start' and a feedback loop input, both using optocouplers with a current of approximately 10mA at 24V DC.
What is the maximum total current for the output circuits of the AS-i Safety Monitor?
The maximum total current for all output circuits is 6A for ASM1/1, ASM1E/1, and ASM2E/1, with each output circuit handling up to 3A. For ASM1/2, ASM1E/2, and ASM2E/2, the maximum total current is 8A, with each output circuit handling up to 3A for the first circuit and 1A for the second circuit.
What is the overvoltage category for the AS-i Safety Monitor?
The AS-i Safety Monitor is rated for overvoltage category 3, which is suitable for a rated operating voltage of 300V AC, in accordance with VDE 0110 Part 1. This ensures protection against transient overvoltages in industrial environments.