How much vertical space does the Sun Enterprise 250 server require?
Each Sun Enterprise 250 server requires six rack units (10.5 inches, 26.7 cm) of vertical space. A 56-inch cabinet can hold up to four servers, while a 68-inch or 72-inch cabinet can accommodate up to five servers.
What is the minimum clearance required for airflow?
Each Sun Enterprise 250 server needs 28 square inches (175 square cm) of unrestricted airflow at the front and 23 square inches (143 square cm) of unrestricted exhaust at the rear. Maintain at least 1.5 inches (3.8 cm) clearance between the system and any front or rear doors.
What are the rack mounting rail requirements?
The rack must have two pairs of vertical mounting rails (one pair in front, one in back) that conform to the EIA standard. The left-side-to-right-side rail spacing must be 18.3 inches (46.5 cm), and front-to-rear rail spacing must be between 26.875 and 34.875 inches (68.26 to 88.5 cm).
How many people are needed to rackmount the server?
Two people are required to move the chassis and align/install the slide assemblies. The chassis is heavy, and proper handling is essential for safety and stability during installation.
What is the weight of the Sun Enterprise 250 server?
The Sun Enterprise 250 server weighs 118 lbs (53 kg). The rack must firmly support this weight, along with the rackmounting hardware and any other installed devices.
What is the front protrusion of the server when mounted?
When mounted, the Sun Enterprise 250 server extends 2.3 inches (5.84 cm) forward of the front vertical mounting rails. The enclosure extends 28.25 inches (71.76 cm) from the front face to the rearmost point.
What is the recommended service access area for the rack?
A minimum of 3 feet (1 meter) deep and 6 feet (2 meters) wide area must be available in front of the rack for installation and service access. When fully extended, the system will protrude 29.75 inches (75.6 cm) forward of the front vertical mounting rails.
What are the EMI shielding requirements?
The system chassis and metal side panels provide electromagnetic interference (EMI) shielding. These components remain in place when the unit is rackmounted, ensuring compliance with EMI standards.
What anti-tip protection is required for the rack?
The rack must be securely bolted to the floor or equipped with a sturdy and extendable anti-tip leg. This prevents tipping forward when servers and other devices are fully extended from the front of the rack.
What fire containment standards must the rack enclosure meet?
The rack enclosure must meet Underwriters Laboratories, Inc. and TUV Rheinland of N.A. requirements for fire containment to ensure safety in case of fire incidents.