Product description:
Frequently Asked Questions
How do I install the PSTX softstarter?
Install the PSTX softstarter using M6 bolts or bolts of the same dimension and strength. Ensure the enclosure size is not smaller than the minimum recommended. Verify the drilling plan and make sure there is free airflow through the product. If removing the HMI for remote control, drill a hole and use an RJ45 cable with a maximum length of 3 meters.
What are the electrical specifications of the PSTX softstarter?
The PSTX softstarter has a rated insulation voltage of 600 V / 690 V, a rated operational voltage of 208-600 / 690 V at 50 / 60 Hz, and a rated control supply voltage of 100-250 V at 50 / 60 Hz. It supports a voltage tolerance of +10% to -15% and a frequency tolerance of ±10%.
How do I connect the PSTX softstarter?
Connect the main circuit by linking terminals 1L1 - 3L2 - 5L3 to the line side and terminals 2T1 - 4T2 - 6T3 to the motor side. Ensure the control supply voltage is applied before connecting the operational voltage. Connect the functional earth to terminal 22 and ensure the earthing cable is as short as possible, with a maximum length of 0.5 meters.
What are the safety precautions for installing the PSTX softstarter?
Always ensure the power is turned off and locked out before starting any work. Use only authorized personnel for installation and electrical connections. Avoid using shielded cables and ensure no liquids, dust, or conductive parts enter the softstarter to prevent damage.
How do I configure the PSTX softstarter?
After connecting the softstarter, switch on the control supply voltage and configure the parameters as described in chapter 6 of the manual. Ensure the operational voltage and control supply voltage match the softstarter's ratings. Use the HMI for local control or remote control via fieldbus.
What communication options are available for the PSTX softstarter?
The PSTX softstarter includes an RS485 physical interface (terminals 23 and 24) for Modbus RTU communication. This allows control of the softstarter, retrieval of status information, and uploading/downloading parameters. The interface can be connected to external devices supporting RS485-based communication.
How do I use the HMI for local control?
Use the HMI for local control by switching the remote/local key to local mode. The HMI includes navigation keys for menu navigation, a start key to initiate motor operation, and a stop key to stop the motor according to set parameters. The HMI also provides information about the softstarter's status and settings.
What are the terminal connections for the PSTX softstarter?
The PSTX softstarter has various terminal connections, including start/stop circuits, programmable inputs, and signal output relays. The analog output terminals (29 and 30) support configurable signals with specific load resistance requirements. The PTC/PT100 temperature sensor inputs are available on terminals 25, 26, and 27.
What are the recommended fuse and circuit breaker specifications?
Use a 6 A delayed fuse for the control supply circuit with C characteristics. The product should only be used within specified ratings, considering ambient temperature and altitude. For short circuit protection, refer to the provided manual and online resources for detailed recommendations.
What are the environmental considerations for the PSTX softstarter?
The PSTX softstarter is designed for environment A. Use in environment B may cause electromagnetic disturbances, requiring mitigation measures. Ensure the ambient temperature does not exceed 40 °C (104 °F) and the altitude does not exceed 1000 m (3281 ft). Derating is required for higher temperatures and altitudes.
Related products from ABB
Busch-ControlTouch
User manual 2 pages
CBX-8R8-H
User manual 2 pages
CBX-8R8
User manual 2 pages
CBXi-8R8
User manual 2 pages
CBXi-8R8-H
User manual 2 pages
TZIDC-110
User manual 2 pages
RC/A8.2
User manual 48 pages
RC/A8.2
User manual 48 pages
NextMove e100
User manual 60 pages
NextMove ESB-2
User manual 60 pages
PSTX1250
User manual 258 pages