How to connect the thermostat to the power supply?
Connect the incoming live and neutral wires to terminal 1 and 2. Ensure the relay terminals 3 and 4 are connected to the load. A fuse is required for terminal 1 if operating at 230 V.
How to connect temperature sensors?
Connect sensor A to terminals 5 and 6, and sensor B to terminals 7 and 8. For humidity sensor C, connect it to terminals 12 and 13. Use the appropriate cables based on temperature range.
What are the temperature ranges for the sensors?
Sensor A operates between -15 °C and +75 °C, Sensor B between +0 °C and +170 °C, and the humidity sensor between -9 °C and +10 °C. Ensure cables are suitable for the temperature range.
How to access the main menu?
Press the navigation button to enter the main menu. The main menu includes three submenus: TEMP, PROGRAM, and SYSTEM. Use the arrow keys to navigate and select options.
What are the available operating modes?
The thermostat supports multiple modes: HEATING (V), COOLING (K), INDUSTRIAL (I), and MAX/MIN (M). These modes can be selected in the PROGRAM submenu for different applications like home, office, or hotel.
How to set the temperature range for heating?
In the TEMP submenu, set the desired temperature range using the up and down arrows. The default range is +5 °C to +45 °C, but it can be adjusted for specific applications like vacation or hotel use.
How does the thermostat respond to input signals?
The thermostat switches to the set temperature when the input is closed. When the input is opened, it returns to the previous temperature setting after any set delay time. This ensures stable control of the system.
What is the function of the humidity sensor?
The humidity sensor (connected to terminals 12 and 13) can be used for humidity control. It works with a single temperature sensor and can be combined with the MAX/MIN mode for precise climate control.
How to reset the thermostat settings?
Use the SYSTEM submenu to reset the thermostat. This will restore default settings for temperature ranges, modes, and other parameters. Ensure the device is powered off before resetting.
What are the display options in the thermostat?
The thermostat display shows the current temperature, setpoints, and status indicators. It also displays system information like alarm status, mode selection, and sensor connections when in the VISUAL mode.