Product description:
Frequently Asked Questions
How do I set up the AP10?
To set up the AP10, connect the Ethernet cable to the Ethernet port of the AP10. If possible, connect to the same network as the viewLinc Enterprise Server. If the Ethernet cable does not provide power, connect the DC power supply. Use the touch interface to complete the setup wizard, configure network settings, and select a VaiNet channel. Ensure the access point is synchronized with an NTP server before enabling Installation Mode.
What is the maximum number of data loggers the AP10 can connect?
The AP10 can connect up to 32 RFL100 Data Loggers to the Vaisala viewLinc Monitoring System. Each access point must have a unique VaiNet channel assigned to it to ensure proper communication and avoid interference.
How do I access the web interface of the AP10?
To access the web interface, first verify the IP address of the AP10 from the touchscreen interface. Open a web browser and enter the IP address in the address field, preceded by 'https://'. Log in using the default credentials: username 'apadmin' and password 'ap123456'.
What are the power options for the AP10?
The AP10 can be powered using Power over Ethernet (PoE) through the Ethernet connector or via the included AC/DC adapter connected to the power supply connector. If both power sources are connected, the AC/DC adapter is used to power the device.
What is the wireless range of the AP10?
In a typical indoor space, the wireless range of the AP10 is at least 100 meters (328 feet). In an open space with line-of-sight and no interfering structures, the range can extend over 500 meters (1640 feet). The range may be affected by walls, ceilings, and large metal surfaces.
What is the default password for the AP10 touchscreen?
The default password for the touchscreen interface of the AP10 is 'ap123456'. This password can be used to lock the touchscreen and access additional settings such as display and LED configurations.
What is the recommended mounting height for the AP10?
The AP10 should be mounted securely, especially if it is placed higher than 2 meters (approximately 6 feet) or in a location where it could pose a hazard if dropped. Ensure the unit is fixed firmly to prevent accidental damage or injury.
How do I configure the network settings for the AP10?
To configure the network settings, use the touch interface to select either Dynamic IP (DHCP) or Static IP. If using DHCP, the access point will automatically receive network configuration settings. For a Static IP, enter the IP address, Subnet mask, and Default gateway as provided by your IT administrator.
What should I do if the AP10 is not synchronizing with the NTP server?
If the AP10 is not synchronizing with the NTP server, ensure it has a network connection to one of the configured NTP servers. Connecting to the default NTP servers requires Internet access, and the network firewall must allow the access point to connect to UDP port 123. An NTP connection error may persist for up to 15 minutes even if the servers are reachable.
What are the safety considerations for installing the AP10?
When installing the AP10, ensure it is securely mounted, especially at heights or in hazardous locations. Avoid placing the AP10 near large metal surfaces, as they may reduce the range of the radio signal. Always use the correct mounting method and ensure the power supply is properly secured to prevent falls or damage.