Product description:
Frequently Asked Questions
How many outputs are available on the Danfoss Icon™ Master Controller 24V?
The Danfoss Icon™ Master Controller 24V provides either 10 or 15 outputs, depending on the model.
What is the purpose of the PWR1 output on the Danfoss Icon™ Master Controller 24V?
The PWR1 output is intended for use in installations with a circulation pump. It provides a live 230 V output (maximum 100 W) that activates when heat is demanded by at least one thermostat. It turns off when no heat is needed to save energy.
What is the function of the potential free relay (RELAY) on the Danfoss Icon™ Master Controller 24V?
The potential free relay (RELAY) can be used to activate heat demand or production from a boiler. It is recommended to use it as the heat demand signal for all boilers with appropriate input capabilities.
How is the Danfoss Icon™ Master Controller 24V connected to a wired thermostat?
For wired thermostats, connect them using a 24 V thermal actuator. The system supports both BUS and Star configurations. In BUS wiring, connect the thermostat to the Master Controller, while in Star wiring, connect the thermostat directly to the power supply.
What is the role of the Radio Module on the Danfoss Icon™ Master Controller 24V?
The Radio Module is required for wireless installations and connects to the Master Controller via an RJ 45 connector. It enables communication between the Master Controller and wireless thermostats and actuators, and comes with a 2-meter patch cable.
What are the different operation modes available on the Danfoss Icon™ Master Controller 24V?
The Danfoss Icon™ Master Controller 24V offers two main operation modes: PWM+ and On/Off. PWM+ divides heat demand into smaller duty cycles to minimize overheating and automatically balances flow to different rooms. On/Off uses hysteresis control to turn the heat on and off based on temperature thresholds.
How do you assign actuator outputs to a thermostat on the Danfoss Icon™ Master Controller 24V?
Use the output selector keys to assign actuator outputs to a thermostat. Each output terminal can connect to only one actuator wire, and you can assign as many outputs as needed to a single thermostat.
What is the purpose of the Expansion Module on the Danfoss Icon™ Master Controller 24V?
The Expansion Module (code no. 088U1100) is required to configure the Danfoss Icon™ Master Controller 24V for applications beyond the basic floor heating system. It allows for more complex setups and can replace the removable lid for special applications.
What is the function of the Installer key on the Danfoss Icon™ Master Controller 24V?
The Installer key is used during system setup to assign thermostats, configure the system, or remove components. It also allows running tests like Network, Application, or Flow tests to finalize the installation.
How do you access the 230 V section of the Danfoss Icon™ Master Controller 24V?
The 230 V section is accessed through a removable lid. To open it, remove the screw and slide the lid out. This section contains the 230 V terminals and can be replaced with an Expansion Module if special applications are required.
Related products from Danfoss
EKC 201
User manual 6 pages
EKC 301
User manual 6 pages
Optyma Plus
User manual 36 pages
Optyma Plus
User manual 40 pages
VRH 120
User manual 4 pages
VRH 60
User manual 4 pages
EKC 102B
User manual 8 pages
EKC 102C
User manual 8 pages
ERC 211
User manual 152 pages
ERC 214
User manual 152 pages
ERC 213
User manual 152 pages
ECL Comfort 210
User manual 36 pages
ECL Comfort 310
User manual 36 pages
AK-PC 551
User manual 12 pages
ECL Comfort 296
User manual 36 pages
EKC 202D
User manual 12 pages
EKC 202D
User manual 12 pages
EKC 302D
User manual 12 pages
EKC 315A
User manual 12 pages
EKC 315A
User manual 12 pages