What is the maximum temperature the heat exchanger can reach?
The heat exchanger's maximum temperature is approximately 500 °C. The appliance may be installed in an area where the ambient temperature lies between -10°C and 40 °C.
What are the requirements for the flue gas exhaust system?
The flue gas exhaust system must have a minimum 3° pitch from the appliance. The maximum length of the intake and flue pipe is six metres incl. 2x2 90° bends. Each additional right-angled bend shortens the length by 2 metres. If possible, use bends of 45°.
What is the correct gas connection procedure?
The gas pipeline and gas tap must comply with local and/or national regulations. The gas tap must be positioned within reach of the appliance. If the connection line is subject to pressures above 60mbar, this gas tap must be closed. Always blow through the gas pipe in compliance with the regulations prior to operating the appliance.
How should the appliance be positioned for installation?
Place the appliance on a sufficiently solid structure, taking into account the minimum free space required. Use the M10 suspension points. Ensure there is enough space for cleaning the burner and flue gas fan.
What is the correct procedure for starting up the appliance?
Switch off the electricity mains switch. Set the room thermostat to the minimum temperature. Open the gas stop cock, then carefully purge the gas pipes and check for leaks. Close the gas stop cock. Switch on the electrical mains switch and set the room thermostat to the maximum temperature. After a pre-purge period, the automatic ignition control will produce an electric arc on the pilot burner and the gas control unit safety valve will open.
How should the air filter be maintained?
Filters on the suction side should be cleaned regularly, as often as once a week if necessary. If the filters are very dirty, they should be replaced by filter fabric of the same quality and designation. If an air filter is fitted, a dirty filter sensor should always be fitted. This pressure switch will switch off the burner when the filter is dirty.
What are the safety precautions when using the appliance?
If you smell gas, it is expressly prohibited to ignite an appliance, touch electrical switches, or telephone from the area in question. Take the following action: switch off the gas and electricity, activate the operational emergency plan, and evacuate the building if necessary.
What is the correct procedure for shutting down the heater?
For short periods of time, set the room thermostat to the minimum temperature and do not switch off the electricity mains switch as this may damage the maximum temperature and safety thermostat. For longer periods of time, set the room thermostat to the minimum temperature and after ± 5 min., the electrical power may be switched off.
What are the maintenance requirements for the appliance?
The appliance must be subjected to maintenance at least once a year, more often if necessary. When carrying out maintenance, the appliance must have been shut down for an extended period. Make sure that you comply with all safety rules. Clean the burner tray, heat exchanger, air discharge louvres, flue gas fan, and V-belt pulleys as needed.
What are the fault codes and their meanings?
Fault codes such as 01 (Ignition failure), 02 (Gas valve relay/T max.), and 03 (Gas valve) indicate specific issues with the appliance. If a different failure code appears on the room thermostat display, please contact the device supplier for assistance.
Related products from Mark
50-9
User manual 20 pages
30-9
User manual 20 pages
Infra
User manual 57 pages
Infra
User manual 64 pages
40-9
User manual 20 pages
GD
User manual 92 pages
GD
User manual 102 pages
GSD
User manual 92 pages
GSD
User manual 102 pages
GND
User manual 92 pages
GND
User manual 102 pages
GSE
User manual 40 pages