Product description:
Frequently Asked Questions
How does the SonicControl measure fat layer thickness?
The SonicControl uses an ultrasonic sensor to measure the fat layer thickness with centimeter precision. This allows for accurate monitoring of the fat layer height in KESSEL fat separators.
What safety precautions should be taken during installation?
Ensure the device is installed in a dry and frost-free location, away from direct sunlight. Always disconnect the power before performing any maintenance or repairs. The device contains electrical voltages, and improper handling can lead to serious injury or death.
How to mount the control unit?
Mount the control unit on a wall using two horizontal holes with a diameter of 6 mm, spaced 168 mm apart. Use 4.5 x 35 mm (TX20) screws to secure it flush against the wall. Ensure there is enough space for access to the cover.
How to install the sensor and sensor holder?
Attach the sensor to the sensor holder using a PE pipe clamp. Secure the sensor holder to the outlet structure with a torque of 1 Nm. Ensure the sensor is properly clipped in place and the mounting holes are aligned with the template provided.
What are the maximum fat layer thickness values for different models?
Maximum fat layer thickness values vary by model. For example, the Euro 'G' model has a maximum of 50 cm, while the Euro 'D' model also has a maximum of 50 cm. These values are based on the recommended sludge layer thickness, which is 50% of the sludge capacity.
How to adjust the fat layer level in the control unit?
Adjust the fat layer level using the 'Parameter -> Level Calibration' option in the settings menu. This is necessary if mechanical adjustments are not possible. The parameters are password-protected, so contact KESSEL's customer service for assistance.
What is the purpose of the sensor holder?
The sensor holder is used to securely mount the ultrasonic sensor on the outlet structure. It ensures the sensor is correctly positioned for accurate measurement and easy access for maintenance.
How to connect the electrical wiring for the device?
Follow the wiring diagram provided in the manual. Ensure all connections are secure and insulated. The device requires a potential-free contact and must be connected according to the local electrical standards and regulations.
What should be done after installing the fat separator?
After installation, fully fill the fat separator with water and check the installation height. Ensure the SonicControl displays '0 cm' when performing a manual operation. If mechanical adjustment is not possible, adjust the level using the calibration settings.
What are the technical specifications of the SonicControl?
The SonicControl has an IP68-rated ultrasonic probe, a battery-backed alarm for power outages, and can be combined with all KESSEL fat separators. It includes free software for data analysis and has a built-in temperature monitoring system for the wastewater.