Product description:
Frequently Asked Questions
How to install the control unit?
The control unit must be installed in a dry and frost-free location, preferably in the house where alarm messages can be easily noticed. Avoid direct sunlight. Ensure sufficient wall distance on the right side to allow for a lid opening. Use two horizontal holes with a diameter of 6 mm, spaced 168 mm apart. Insert the plastic anchors into the holes and tighten the screws to secure the unit.
How to mount the sensor and sensor holder?
Mount the sensor and sensor holder by first marking two holes of 5.5 mm diameter on the outer side of the outlet structure. Drill these holes and secure the sensor holder with a torque of 1 Nm. Use the provided pipe clamps to attach the sensor to the holder and ensure the sensor is clipped into place.
What are the installation dimensions for the sensor?
The installation dimensions for the sensor depend on the specific model. For example, for the Euro 'G' model, the maximum sludge layer thickness is 50 cm, with a recommended warning level at 25 cm. The distance between the upper edge of the lower 'finger' and the lower edge of the outlet (water line) is 2 cm. Always refer to the provided table for exact measurements based on the model.
What is the purpose of the ultrasonic sensor?
The ultrasonic sensor is used for precise centimeter-level measurement of the fat layer height in KESSEL fat separators. It ensures accurate monitoring of the fat layer and can be combined with all KESSEL fat separators. The sensor is protected with an IP 68 rating, making it suitable for harsh environments.
How to perform a manual operation?
Manual operation can be performed using the control unit's maintenance menu. This allows for testing the system without power, checking sensor functionality, and adjusting parameters. Ensure the system is disconnected from power before initiating manual operation. Follow the on-screen instructions to navigate through the menu and perform the required actions.
What are the safety precautions during installation?
During installation, ensure the system is disconnected from power to avoid electrical hazards. Check that all electrical cables and components are in good condition. Do not install the control unit in explosive areas. Follow local electrical codes and ensure proper grounding and protection against short circuits. Always follow the safety guidelines provided in the manual.
How to calibrate the fat layer height?
Calibration of the fat layer height is performed through the 'Parameter -> Level Calibration' section in the control unit's settings. Ensure the fat separator is completely filled with water and check that the SonicControl displays '0 cm' during manual operation. If mechanical adjustment is not possible, adjust the calibration settings in the parameter menu. This process requires a password, so contact KESSEL's customer service for assistance.
What are the technical specifications of the device?
The SonicControl device features an ultrasonic sensor for precise fat layer measurement, a battery-backed alarm for power outages, and IP 68 protection for the sensor. It can be combined with all KESSEL fat separators and includes a free software package for data analysis. The device operates with a potential-free contact and supports various installation configurations, including DIN 4040 and Euro standards.
How to access the maintenance menu?
To access the maintenance menu, navigate through the control unit's settings using the on-screen interface. The maintenance menu allows for manual operation, testing, and maintenance scheduling. It also includes options for viewing current measurements, maintenance history, and system diagnostics. Ensure the device is powered off before accessing the maintenance menu to avoid data corruption.
What is the purpose of the alarm system?
The alarm system provides warnings for critical fat layer levels, ensuring timely maintenance and preventing overflow. It is battery-backed to function during power outages. The alarm can be configured to trigger at specific thresholds, and the system can be set to send alerts via the included software. Regularly check the alarm settings to ensure they align with operational requirements.