Stahl 9440/22-01-21 (68 pages)
Tags
Languages available:
No exact matches found. Please change your query
Need help?
Do you have a question about the product that is not answered in the manual?
- Receive updates on solutions
- Get answers to your question
Product description:
Frequently Asked Questions
What is the purpose of the CPU & Power Module for Zone 1/Div. 1?
The CPU & Power Modul (CPM) serves as a gateway between the internal bus of an IS1+ field station and the fieldbus, connecting it to the automation system in either simple or redundant configurations.
What are the technical specifications for power supply?
For 9440/22-01-11: nominal voltage is 24 V DC with a range of 20–35 V DC. For 9440/22-01-21, it operates on AC voltages between 90 and 253 volts at frequencies of 50 or 60 Hz.
What safety certifications does the device have?
The module is certified for IECEx, ATEX, EAC (TR), Brazil (INMETRO), India (PESO), Canada (CSA), Serbia (SRPS), and USA (FM). It also has mutual recognition certificates from various classification societies.
How should the device be installed in hazardous areas?
The module must only be installed in zones or divisions it is certified for, such as Zone 1/Div. 1, Zone 2/Div. 2, and Zones 21-22. It requires a housing that meets IEC/EN standards depending on the zone.
What are the maximum electrical parameters for fieldbus communication?
The maximum voltage is 3.7 V for Uo and +/-4.2 V for Ui, with current up to 134 mA and power of 124 mW on the fieldbus and service bus (RS485-IS).
What are the recommended maintenance practices?
Only perform maintenance as described in this manual by qualified personnel. Clean only with a damp cloth to avoid static buildup, and ensure all connections meet IP30 protection standards.
How should unused cables be handled during installation?
Unused conductors at the socket must be isolated using cable ends or Ex-e terminals. Maintain minimum distances of 50 mm between safe and non-safe circuits to prevent interference.
What are the safety requirements for handling hazardous areas?
Only qualified personnel should handle installation, maintenance, or repairs in explosive zones. Ensure all operations follow IEC/EN standards like IEC/EN 60079-14 and use proper isolation between circuits.
What is the maximum number of I/O modules that can be connected?
The module supports up to eight I/O modules, with power consumption increasing accordingly. Ensure all connections are within specified limits for safe operation.
How should faults or errors be addressed during operation?
Refer to the error correction section in this manual for troubleshooting steps and status indicators. Always ensure that any fault is resolved before continuing operations to prevent further damage.